Ultrasonic Level Sensor

The UL7 series sensor based on the ultrasonic technology provide a non-contact method of detecting level measurements. It’s a member of Cross Smart Sensor family which can work independently by 24VDC power supply and output RS485 digital signal with Universal Modbus-RTU protocol. It means that the UL7 sensor can be connected to all devices commonly used (Data logger, PLC, DCS …) and suitable for sensor network applications. It's recommended to work with GDC (General Displayer & Controller) series if a remote monitor is required. UL7 can be calibrated/configured by GDC or by computer with software.

This versatility makes them deal for a variety of applications. Ultrasonic sensors are not affected by target surface, color or translucency and they function extremely well in harsh environments. When monitoring liquids, they are not affected by changes in dielectric constant, specific gravity or viscosity.

When connect to GDC terminal, it gives real time reading, analog outputs and relays for field control. It also can be used as open channel flow meter if ordered with the OCF software of GDC which has built-in standard flume measuring formulas, such as: Parshall flume, V flume, Venturi flume and Rectangle flume...

FEATURES AND BENEFITS

● Automatic temperature compensation
● Blind Zone adjustable
● PVDF Sensor Face for chemically aggressive environments
● Open Protocol for sensor network applications
● ViewTM software available

APPLICATIONS

● Water & Waste Water Treat Plant
● Storage Tank Levels
● Effluent pits
● Reservoir Level
● Buffer Tanks
● Open Channel Flow

TECHNICAL DATA

Range Level: 33ft. (10m) std. Optional 50ft. (15m) or 66ft. (20m)
Flow: 0.20 m3/h ~ 200.000.00m3/h (work with GDC for Open Channel Flow)
Accurate ±0.25%FS
Resolution 0.04in (1mm)
Angle 8°@3db
Blind Zone 12ft. (0.3m) @ 33ft.; 20ft. (0.5m) @ 50ft. & 66ft.
Temp. compensation Automatic
Respond Time 0.5s
Operate Temp. -40 to 158°F (-40 to 70°C)
Protection NEMA 4X, NEMA 6P, IP68
Pressure 2bar
Material PVC housing and PVDF sensor face
Process Connection 1”NPT
Cable Standard 10’, Max. 650’
Power Supply 24VDC by GDC or individual power source. Consumption < 6w
Output RS485 Modbus RTU
Weight with 33ft. cable: R10: 43.0oz (1.22kg); R15/20: 53.3oz (1.51kg)
CE Marking EN 61326-1:2013 Electromagnetic Compatibility EMC

           DIMENSION                                                                     WIRING

                                          

R10: 4.8in (122mm) x 3.1in (79mm)
R15/R20: 4.8in (122mm) x 3.8in (97mm)